BH-DC-PMA101R
BH-DC-PMA300R
In order to operate the permanent magnetic actuator built into reclosers or fault interrupters, a lot of energy must be supplied to the tripping or closing coil instantaneously, and sufficient energy must always be stored in the capacitor banks for this purpose.
In the case of devices that perform the reclose sequence, such as reclosers, the ability to quickly charge the capacitor banks is also required to perform the reclose and protection operation according to the set reclose sequence.
BH-DC-PMA series drive modules consist of a DC/DC converter for charging capacitor banks and an output part consisting of a large-capacity IGBT for supplying the energy charged in the capacitor banks to the tripping and closing coil of the magnetic actuator.
Item | BH-DC-PMA101R | BH-DC-PMA200R | BH-DC-PMA300R |
---|---|---|---|
Rated Input Range | 18~38Vdc | 18~38Vdc | 75~135Vdc |
Rated Input Current | 35A at 24Vdc | 35A at 24Vdc | 35A at 24Vdc |
Rated Charging Capacity | 125V/6.A | 125V/6.A | 125V/6.A |
Output Voltage Adjustment Range | 90~160Vdc | 90~160Vdc | 90~160Vdc |
IGBT Output | 1200V/120A at Tc=110ºC | ||
Dimensions (mm) | 258 x 145 x 50 | 268 x 145 x 50 | 2530 x 170 x 50 |
Applications | Circuit breakers with one magnetic actuator, such as reclosers |
Circuit breakers with two or more magnetic actuators, such as RMUs |
GIS control panels for controlling magnetic actuators through button operation |
AC/DC SMPS power supply.
Capacitor bank for magnetic actuator.
BR-10R/RN series recloser control.
SF6 gas insulated recloser.
BR10-PR series solid insulated recloser.
Padmount switchgears
BH SYSTEM249-14, Soltaesangdu-gil, Hyangnam-eup, Hwaseong-si, Gyeonggi-do, KOREA